?Cuáles son las normas de aceptación de puertas cortafuegos de JIAHUI?
?Q: What are the key acceptance criteria for JIAHUI fire doors during installation and final inspection???
?A:?? JIAHUI fire doors must comply with rigorous national and industry standards to ensure fire integrity, structural stability, and operational reliability. The acceptance process spans three phases: ?pre-installation checks, ?installation execution, and ?post-installation validation. Below are the critical criteria:
?1. Pre-Installation Preparation?
?Dimensional Compliance:
Wall opening dimensions must be verified before installation, with tolerances ??≤±5mm? in width/height. Deviations exceeding this require structural correction prior to door fitting.
?Embedded Components:
All pre-embedded steel plates (e.g., anchor points) must undergo ?full-penetration welding. Welded joints require complete anti-rust coating (e.g., epoxy primer) to prevent corrosion.
?2. Installation Execution?
?Alignment Precision:
Vertical deviation of the door frame: ??≤3mm per meter? (measured with a laser level).
Horizontal deviation: ??≤2mm per meter? (checked via precision level).
Frame misalignment compromises sealing and must be rectified immediately.
?Gap Management:
Clearance between door leaf and frame must be ??≤3mm? on all sides (hinge, lock, top). Gaps exceeding this require adjustment or reseating. All seams must be filled with ?intumescent fire sealant? (e.g., graphite-based strips) to block smoke/flame penetration.
?Closer Calibration:
After installation, door closers must enable automatic closure when the door is opened ?**≥90°. Closers failing to reset within ??≤60 seconds**? or exhibiting resistance >80N force are non-compliant.
?3. Final Inspection & Testing?
?Comprehensive Functional Checks:
?Seals: Fire-resistant seals (e.g., ceramic silicone strips) must adhere fully to the frame with ?zero gaps or peeling.
?Hardware: Hinges, locks, and closers must operate smoothly without jamming, deformation, or excessive force (>80N). Apariencia: Las superficies deben estar libres de abolladuras, óxido o defectos de recubrimiento (según GB 12955-2008). Validación de rendimiento de terceros: Las puertas muestreadas por lotes (mínimo 1 por cada 50 unidades) deben someterse a pruebas de laboratorio independientes según GB/T 7633 o ISO 834, que incluyen: Resistencia al fuego: Mantener la integridad estructural y el aislamiento durante la duración nominal (p. ej., 90 min para Grado A). Fuga de humo: Fuga de aire ≤1,5 ??m3/(m·h) a una presión diferencial de 50 Pa. Los informes de las pruebas deben presentarse antes de la aprobación del proyecto. Documentación y cumplimiento Registros obligatorios: Certificaciones de fábrica (aprobación ISO/FM), informes de pruebas de productos y registros de instalación. Certificados de inspección de terceros para耐火性能 (resistencia al fuego) y气密性 (hermeticidad). Manejo de No Conformidades: Las puertas que no cumplen con algún punto de control requieren una solución (por ejemplo, resellado, reemplazo de herrajes) y una nueva inspección. Las fallas persistentes provocan el rechazo del lote.